2.1.4 Measured and calculated pressure levels - recips.
Measuring Min. Max. Factory Note
Suction pressure
(bar)
High shutdown
High alarm
Low alarm
Low shutdown
-
1.5
-1.0
-1.0
-
9.0
6.0
6.0
-
5.0
2.5
1.5
-
3+4+5
3+4+5
3+4+5
Discharge pressure
(bar)
High shutdown
High alarm
Low alarm
Low shutdown
4.0
3.0
-
-1.0
24.0
22.0
-
-1.0
16.0
15.0
-
-1.0
1+6
1+6
-
1+5
Intermediate pressure (bar)
Two stage compressors only
High shutdown
High alarm
Low alarm
Low shutdown
4.0
3.0
-1.0
-1.0
24.0
22.0
10.0
10.0
7.0
6.0
-1.0
-1.0
1+6
1+6
1+6+16
1+6+16
Oil pressure (bar)
Calculated value
SMC100/TSMC/HPC
High shutdown
High alarm
Low alarm
Low shutdown
Low-low shutdown
5.0
5.0
0.5
0.5
0.0
7.0
7.0
5.0
5.0
1.5
6.0
5.5
4.0
3.5
0.5
2+5+16
2+5
2+5+14
2+5+14
2+5+32
Diff. pressure across oil filter
(bar)
Calculated value SMC100/
TSMC/HPC
High shutdown
High alarm
Low alarm
Low shutdown
0.0
0.0
-
-
10.0
7.0
-
-
6.0
4.0
-
-
2+11a
2+11a
-
-
Table 11: Measured and calculated pressure levels - reciprocating compressors
Alarms and shutdowns
40/319
Engineering manual - Unisab III 1.10
001930 en 2014.09

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls SABROE Unisab III Control and is the answer not in the manual?

Johnson Controls SABROE Unisab III Control Specifications

General IconGeneral
BrandJohnson Controls
ModelSABROE Unisab III Control
CategoryControl Systems
LanguageEnglish

Related product manuals