10: Take over (reciprocating compressors)
No
Yes
Select Yes if Unisab III is configured as a reciprocating compressor, operates in a combined
plant of reciprocating and screw compressors and the Take over/transfer function in Multisab
is required.
11: COP active
No
Yes
Select Yes if Unisab III is fitted with a function for COP measuring (Coefficient Of Perform-
ance, i.e. cooling efficiency of compressor). COP measuring requires a flow measuring device
as well as a motor efficiency measuring device. See also Unisab III COP Manual. Select No if
Unisab III is not used for COP measuring.
12: Chiller
No
Yes
Select Yes to use the following build-in functions for chiller control. See section 3.6. Compres-
sor control - chiller functions for a detailed description.
Select Yes to enable the measurement and supervision of the process in temperature input.
The process in temperature will then be displayed in Control values/Process Temp/Values. See
subsection 3.6.5. Flow condenser (ChillPAC/PAC - optional).
Always select No if you do not use chiller functions. See section 3.6. Compressor control -
chiller functions for a detailed description.
When chiller operation is set to Yes the following configuration points 11 to 17 will show up.
13: Oil return sep.
No
Yes
Select Yes to use the oil return from separator function. See subsection 3.6.1. Oil return from
oil separator (ChillPAC).
14: Oil return evap.
No
Yes
Select Yes to use the oil return from evaporator function. See subsection 3.6.2. Oil return
from evaporator (ChillPAC/PAC).
15: By-pass start
No
Yes
Select Yes to use the by-pass start function. See subsection 3.6.3. By-pass function (Chill-
PAC). When choosing by-pass start it will not be possible to configure 16: Level control to LP
or HP.
Set-up
Engineering manual - Unisab III 1.10
001930 en 2014.09
189/319

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls SABROE Unisab III Control and is the answer not in the manual?

Johnson Controls SABROE Unisab III Control Specifications

General IconGeneral
BrandJohnson Controls
ModelSABROE Unisab III Control
CategoryControl Systems
LanguageEnglish

Related product manuals