EasyManuals Logo

Johnson Controls SABROE Unisab III Control User Manual

Johnson Controls SABROE Unisab III Control
322 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #197 background imageLoading...
Page #197 background image
No. Type of regulator Minimum Maximum
Factory
setting
Unit
2 Normal oil cooling
Set point 1/oil temperature
Hysteresis
35 75 50
5 (fixed)
°C
°C
3 HLI/BLI cooling
Set point 1/discharge pipe temperature
Hysteresis
-20 150 65
2 (fixed)
°C
°C
5 3-way valve
Set point 1/oil temperature
Neutral zone
Prop. band oil cooling
35
0
0
75
100
100
50
4
4
°C
°C
°C
6 HLI-AKV oil cooling
Set point 1/discharge pipe temperature
Neutral zone
Prop. band
-20
0
1
150
10
100
65
0
10
°C
°C
°C
7 HLI 4-20 mA oil cooling
Set point 1/discharge pipe temp.
Neutral zone
Prop. band
T.int.
T.diff.
40
0
1
1
0
80
10
100
999
999.9
65
0
30
10
0
°C
°C
°C
sec.
sec.
8 Thermo pump internal
Set point 1/discharge pipe temperature 70 90 80 °C
Table 45: Oil cooling setting - screw compressors
4: Oil controller
I
PID
Select PID for applications where a change in the cooling requirement must be met by a fast
change in cooling capacity. PID is selected as standard.
5: Water cooling (reciprocating compressors)
No
Yes
Water cooling output is activated by rising discharge pipe temperature. The set point for this
value is set in Disch. Temp/Parameter, Set point 1. The set point has a fixed hysteresis of 5K.
Example:
Sp 1 = 100°C:
Cooling starts at 100°C and stops at (100-5) = 95°C.
Water cooling output is closed at compressor stop according to adjustable time delay. In
Timers/Timer setup adjust time delay Oil cool on.
Intermediate pressure liquid injection (Two stage reciprocating compressors)
The intermediate pressure liquid injection for TSMC/TCMO compressors is active whenever the
compressor is configured to TCMO or TSMC. The solenoid valve for intermediate pressure liq-
uid injection is activated when the compressor has started and the discharge pipe tempera-
ture gets too high. The set point for this value is entered in Control values/Discharge/Temper-
ature/Control, Set point 2. The set point has a fixed hysteresis of 5°K.
Set-up
Engineering manual - Unisab III 1.10
001930 en 2014.09
195/319

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls SABROE Unisab III Control and is the answer not in the manual?

Johnson Controls SABROE Unisab III Control Specifications

General IconGeneral
BrandJohnson Controls
ModelSABROE Unisab III Control
CategoryControl Systems
LanguageEnglish

Related product manuals