EasyManuals Logo

Johnson Controls SABROE Unisab III Control User Manual

Johnson Controls SABROE Unisab III Control
322 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #214 background imageLoading...
Page #214 background image
there is no particular cooling requirement. However, if deviation is large the timer will count
down fast and start the compressor.
Example 1: Suction pressure regulation has been selected. The measured suction pressure
equals the set point. The compressor is stopped and ready to start.
Set point Sp = -10°C/R
Nz = 2°C/R
Pb = 5°C/R
Start delay = 60 sec
P band factor start delay = 5.
When the measured suction pressure exceeds -9°C/R, the Start delay timer will start counting
with an interval of 5 seconds (P band factor) each time the value in the display counts one
down. If the pressure steadies, the timer will run for 5 x 60 = 300 seconds.
Should the measuring value reach -6.5°C/R, the counting interval will be 3 seconds. If the
pressure is still moving upwards and exceeds -4°C/R (the Pb limit) the timer will count in sec-
onds. The resulting total delay will range between 60 and 300 seconds and after this the com-
pressor will start.
Example 2: Discharge pressure regulation has been selected on a reciprocating compressor.
The measured discharge pressure equals the set point. The compressor is running at 100%
capacity.
Set point Sp = 30°C/R
Nz = 2°C/R Pb = 5°C/R
Delay down = 30 sec
P band factor delay down = 3.
When the measured discharge pressure exceeds 31°C/R, the timer Delay down will start
counting with an interval of 3 seconds (P band factor) each time the value in the display
counts one down. If the pressure steadies the timer will run for 3 x 30 = 90 seconds.
Should the measuring value reach 33.5°C/R, the counting interval will be 2 seconds. If the
pressure is still moving upwards and exceeds 36°C/R (the Pb limit) the timer will count in sec-
onds.
The resulting total delay will range between 30 and 90 seconds and after this the compressor
will disengage one capacity stage.
Set-up
212/319
Engineering manual - Unisab III 1.10
001930 en 2014.09

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls SABROE Unisab III Control and is the answer not in the manual?

Johnson Controls SABROE Unisab III Control Specifications

General IconGeneral
BrandJohnson Controls
ModelSABROE Unisab III Control
CategoryControl Systems
LanguageEnglish

Related product manuals