No. Value Factory Low High Unit
Adjust-
able
49 PMS delay 0 0 900 Sec. Yes
50 Critical low oil circuit 25 - - Sec. No
51 Start rpm limiter 300 60 3600 Sec. Yes
52 High internal pressure 25 - - Sec. No
53 Fan delay 60 0 1200 Sec. Yes
54 Oil pump low alarm 30 0 600 Sec. Yes
55 Oil pump low shutdown 120 0 900 Sec. Yes
56 Backspin delay 1 0 10 Sec. Yes
Table 49: Timer values - screw compressors