47. Oil return delay
For chiller use only.
At compressor start-up, this timer is used to delay the open/close function for the oil return
valve draining the oil separator.
48. Pump down
For chiller use only.
This timer controls the maximum time the pump down sequence can run after compressor
stop. Pump down is used when the Chiller DX expansion valve control is configured.
This pump down function, where the compressor runs with a closed expansion valve, lets the
compressor run until the suction pressure is below the ”pump down set point” or until the
pump down timer has run out, whichever comes first.
49. PMS delay
After compressor stop it is possible to delay the PMS Start request output signal within the
stated time.
This delay can e.g. be used for pump after-run.
50. Oil pressure low-low delay
For SMC reciprocating compressors.
The low-low oil pressure shutdown will be delayed for the stated time at compressor start.
Set-up
Engineering manual - Unisab III 1.10
001930 en 2014.09
229/319

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls SABROE Unisab III Control and is the answer not in the manual?

Johnson Controls SABROE Unisab III Control Specifications

General IconGeneral
BrandJohnson Controls
ModelSABROE Unisab III Control
CategoryControl Systems
LanguageEnglish

Related product manuals