Starting reciprocating/screw comp ressor in MANUAL mode, continued
Che ck that input
Starting re quest fee dback,
termina ls (X3/19- 20), is closed . Can also be
checked in picture
Service /Diag nosis /
Hardw are/Digital input/P MS feedb ack = 1
.
Press to start compres s or.
Light diode on front flashes
gree n
Che ck emerge ncy s top a nd TÜV
pres sure control, if any. The re
must be conne ction betwee n
terminals (X13/1-10).
Doe s
comp res sor
sta rt?
PMS
error mes-
sage re-
ce ived
Input
closed?
Try a gain
Apply jumper, or che ck conne c-
tions from terminals (X12/17-18)
to power ma na gem ent sys tem .
Is
digital
output c ompress or
motor start
activa ted
when trying to st art
(Digital output
diode no. 1
is on )?
Conta ct
Johnson Co ntrols
Denma rk
Che ck connection from termina ls (X12/
1-2) to motor sta rter
Con nection
OK?
Corre ct wiring
connection
Is there f e ed-
back on termi-
nals (X3/1-2)
from moto r
guard? Digital
input di ode no.
1 is on.
Check pre-fuses a nd control
voltage of motor guard.
1
OK
Corre ct wiring
connection
3
Yes
Yes
Yes
Yes
Yes
Ye s
No
No
No
No
No
No
Fig. 49: Error diagram no. 2
Troubleshooting
288/319
Engineering manual - Unisab III 1.10
001930 en 2014.09

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls SABROE Unisab III Control and is the answer not in the manual?

Johnson Controls SABROE Unisab III Control Specifications

General IconGeneral
BrandJohnson Controls
ModelSABROE Unisab III Control
CategoryControl Systems
LanguageEnglish

Related product manuals