Johnson Controls SABROE Unisab III Control - 2.3. Shutdowns and alarms with identification numbers for screw compressors

Johnson Controls SABROE Unisab III Control
322 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P oil >
[1.5 x P suct ]
+ 1.1 bar
No
No
Low main oil
pressure alarm
Yes
ALARM
No
Yes
Allow load
Reset
t36 = 0
Unload
Yes
t36 > 3 min
C
P oil >
[1.5 x P suct ]
+ 1.0 bar
t36 + 1
Alarm off
B
Fig. 9: Insufficient main oil pressure during low differential pressure, SAB 157HR
C
D
P disch - P oil
> 2.7 bar
Yes
No
No
Yes
Low oil
pressure alarm
ALARM
T37 > 10 min.
reset
t37 = 0
Fig. 10: Oil circuit pressure drop
Note: For SAB 157HR the alarm limit is 1.7 bar.
Alarms and shutdowns
56/319
Engineering manual - Unisab III 1.10
001930 en 2014.09