System going down IMMEDIATELY
...
...
Operating system halted.
Please press any key to reboot.
CAUTION: The nal output of any version of the request system halt command is the
“The operang system has halted.” Although trac and the operang system have
stopped, the PTX10001-36MR power supply LEDs remain lit and a fan module
connues to run. Wait at least 60 seconds aer rst seeing this message before
following connuing with this procedure.
3.
4. Turn o the circuit breaker for the DC power source.
CAUTION: Turn o the circuit breaker for the HVDC power source before
disconnecng the power cord from the power supply. Unplugging an HVDC
connecon while the power supply is powered up might damage the electrical
connectors.
5. Loosen the thumbscrews for the power cable.
6. Disconnect a connector for the power cables or release each of three cables from the power supply
(requires a standard screwdriver).
7. Gently pull out the socket end of the power cable connected to the power supply.
8. Uncable the device before removing it from the rack.