PTX10001-36MR Clearance Requirements for Airow and Hardware
Maintenance
When planning the site for a PTX10001-36MR installaon, you must allow sucient clearance around
the installed chassis (see Figure 19 on page 52).
Figure 19: Clearance Requirements for Airow and Hardware Maintenance for a PTX10001-36MR
Follow these guidelines:
For the cooling system to funcon properly, the airow around the chassis must be unrestricted. See
"PTX10001-36MR Cooling System" on page 21 for more informaon about the airow through the
chassis.
If you are mounng a PTX10001-36MR in a rack with other equipment, ensure that the exhaust from
other equipment does not blow into the intake vents of the chassis.
You must leave at least 24 in. (61 cm) both in front of and behind the PTX10001-36MR for service
personnel to remove and install hardware components. You must leave adequate space at the front
and back of the PTX10001-36MR. NEBS GR-63 recommends that you allow at least 30 in. (76.2 cm)
in front of the rack or cabinet and 24 in. (61 cm) behind the rack.
PTX10001-36MR Physical Specicaons
Table 23 on page 53 lists the physical specicaons for the PTX10001-36MR chassis.