Table 25: Rack Requirements for the PTX10001-36MR
(Connued)
Rack
Requirement
Guidelines
Rack connecon
to building
structure
• Secure the rack to the building structure.
• If earthquakes are a possibility in your geographical area, secure the rack to the oor.
• Secure the rack to the ceiling brackets as well as wall or oor brackets for maximum
stability.
PTX10001-36MR Cabinet Requirements
You can mount the PTX10001-36MR in an enclosure or cabinet that contains a four-post 19-in. open
rack as dened in
Cabinets, Racks, Panels, and Associated Equipment
(document number EIA-310-D)
published by the Electronics Industry Associaon.
Cabinet requirements consist of:
• Cabinet size and clearance
• Cabinet airow requirements
Table 26 on page 56 provides the cabinet requirements and specicaons for the PTX10001-36MR.
Table 26: Cabinet Requirements for the PTX10001-36MR
Cabinet Requirement Guidelines
Cabinet size and clearance The minimum cabinet size for accommodang a PTX10001-36MR device
is 36 in. (91.4 cm) deep. Large cabinets improve airow and reduce the
chance of overheang.
56