General Site Guidelines | 50
PTX10001-36MR Chassis Grounding Cable and Lug Specicaons | 51
PTX10001-36MR Clearance Requirements for Airow and Hardware Maintenance | 52
PTX10001-36MR Physical Specicaons | 52
Site Electrical Wiring Guidelines | 53
PTX10001-36MR Rack Requirements | 54
PTX10001-36MR Cabinet Requirements | 56
PTX10001-36MR Environmental Requirements and Specicaons
The PTX10001-36MR must be installed in a rack or cabinet. It must be housed in a dry, clean, well-
venlated, and temperature-controlled environment.
Follow these environmental guidelines:
The site must be as dust-free as possible, because dust can clog air intake vents and lters, reducing
the eciency of the PTX10001-36MR cooling system.
Maintain ambient airow for normal PTX10001-36MR operaon. If the airow is blocked or
restricted, or if the intake air is too warm, the chassis might overheat, leading to the
PTX10001-36MR temperature monitor shung down the router to protect the hardware
components.
Table 22 on page 49 provides the required environmental condions for normal PTX10001-36MR
operaon.
Table 22: PTX10001-36MR Environmental Tolerances
Descripon Tolerance
Altude No performance degradaon up to 6,562 feet (2000 meters).
49