NOTE: Primary overcurrent protecon is provided by the building circuit breaker. This breaker
must protect against excess currents, short circuits, and earth grounding faults in accordance
with NEC ANSI/NFPA 70.
Ensure that the polarity of the DC input wiring is correct. Under certain condions, connecons with
reversed polarity might trip the primary circuit breaker or damage the equipment.
The marked input voltage of –48 VDC for a DC-powered device is the nominal voltage associated
with the baery circuit, and any higher voltages are only to be associated with oat voltages for the
charging funcon.
Because the device is a posive ground system, you must connect the posive lead to the terminal
labeled RTN, the negave lead to the terminal labeled –48 VDC, and the earth ground to the device
grounding points.
DC Power Copper Conductors Warning
WARNING: Use copper conductors only.
Waarschuwing Gebruik alleen koperen geleiders.
Varoitus Käytä vain kuparijohmia.
Aenon Ulisez uniquement des conducteurs en cuivre.
Warnung Verwenden Sie ausschließlich Kupferleiter.
Avvertenza Usate unicamente dei conduori di rame.
Advarsel Bruk bare kobberledninger.
Aviso Ulize apenas os condutores de cobre.
¡Atención! Emplee sólo conductores de cobre.
Varning! Använd endast ledare av koppar.