• Install the device in a secure area, so that only authorized personnel can access the device.
PTX10001-36MR Chassis Grounding Cable and Lug Specicaons
For installaons that require a separate grounding conductor to the chassis, the PTX10001-36MR must
be adequately grounded before power is connected to ensure proper operaon and to meet safety and
electromagnec interference (EMI) requirements. To ground a PTX10001-36MR, connect a grounding
cable to earth ground and then aach it to the chassis grounding points.
WARNING: The device is a pluggable type A equipment installed in a restricted-access
locaon. It has a separate protecve earthing terminal provided on the chassis in
addion to the grounding pin of the power supply cord. This separate protecve
earthing terminal must be permanently connected to earth ground for installaons that
require a separate grounding conductor to the chassis.
WARNING: To comply with GR-1089 requirements, all intrabuilding copper cabling
used for transceiver ports must be shielded and grounded at both ends.
CAUTION: Before device installaon begins, a licensed electrician must aach a cable
lug to the grounding cables that you supply. See "Connect the PTX10001-36MR to
Ground" on page 86. A cable with an incorrectly aached lug can damage the
PTX10001-36MR.
Before connecng the PTX10001-36MR to earth ground, review the following informaon:
• The grounding lug required is a Panduit LCD6-14AH-L or equivalent (not provided).
• The grounding cable that you provide for a PTX10001-36MR must be the same size or heavier than
the input wire of each power supply. Minimum recommendaons are 8 AWG (8.4 mm²) stranded
wire, 90° C wire, or as permied by local code.