6. Function Description
6-36
6.4 Function group (FUN_[][])
6.4.1 Jump code (FUN_00)
Jumping directly to any parameter code can be accomplished using FUN_00 [Jump code].
Press [PROG] key first and set 2 using [
▲
(Up)], [
▼
(Down)], [SHITF/ESC] and press [ENT] key to jump to FUN_02. If
the desired code cannot be accessed or void, it automatically jumps to closest code.
After jumping, it is available to jump to other codes using [▲(Up)], [▼(Down)].
6.4.2 Operating method select
1) FUN_01(RUN/STOP source select)
There are four methods for issuing RUN/STOP command of the motor.
z Terminal 1/ Terminal 2: Digital input of the FX/RX terminal
z Keypad: [FWD], [REV], [STOP] key on the keypad
z Option: using Option card. (Factory setting: Terminal 1)
Code LCD display Description Setting range Unit
Factory
setting
FUN_01 Run/Stop Src RUN/STOP source select
Terminal 1
Terminal 2
Keypad
Option
Terminal 1
Difference between Terminal 1 and Terminal 2 setting
Run/Stop source select Terminal ON/OFF FWD/REV select
ON FWD run command
FX
OFF Stop command
ON REV run command
Terminal 1
RX
OFF Stop command
ON Run command
FX
OFF Stop command
ON REV rotation
Terminal 2
RX
OFF FWD rotation
For Analog speed setting, applying (+) Voltage marks FWD Run command and (-) voltage REV Run command.
Analog speed setting
range
FX / FWD / Option FWD RX / REV / Option REV
0 ~ +10 V Forward direction Reverse direction
-10 ~ 0 V Reverse direction Forward direction
FUN▶ Spd Ref Sel
02 Analog