6. Function Description
6-24
6.3 Parameter Group (PAR_[][])
6.3.1 Jump code (PAR_00)
PAR_00, jumping directly to any parameter code can be accomplished.
(Example) Moving to PAR_30
Press [PROG] and set to 30 using [SHIFT/ESC] / [▲(Up)] / [▼(Down)] and press [ENT] key. If the desired code
cannot be set (void), the nearest code will be displayed.
Use [▲(Up)] / [▼(Down)] to move to other codes.
6.3.2 Parameter group function
1) PAR_01 (Parameter initialize)
This is used to initialize all parameters or each group back to the factory defaults. After performing this, be sure to
check PAR_07 (Motor Select) is properly set.
Code LCD display Description Setting range Unit
Factory
setting
PAR_01 Para. init
Initialize parameters as factory
defaults
No
All Groups
DIS
DIO
PAR
FUN
CON
EXT
AIO
USR
2ND
E/L
SYN
WEB
No
2) PAR_02 ~ 03 (All Parameter Read/Write)
Parameters setting can be copied to other inverters using keypad. To do this, set PAR_02 ‘Parameter Read’ to “Yes”
to upload the parameter setting from the inverter. Take the keypad out and install it to the copied inverter and set
PAR_03 ‘Parameter Write’ to “Yes” to download the function parameters.
Code LCD display Description Setting range Unit
Factory
setting
PAR_02 Para. Read All Paramter Read No/Yes No
PAR_03 Para. Write All Paramter Write No/Yes No
PAR▶ Rs
30 0.346 ohm