4. Trial Operation
4-9
4.5.3 Standstill auto tuning
1) Precaution
Be sure to lock the motor shaft using magnetic brake.
2) StandStill Type Auto-tuning procedure
LCD Display Description Tuning Time
Set the auto-tuning type to “Standstill”. -
Auto-tuning starts if ALL1 is set. -
Stator resistance (R
s
) is measured
without rotating the motor.
20-30 Sec
The leakage inductance (sL) of the
motor is measured without rotating the
motor.
90-150 Sec
Flux current (IF), rotor time constant (T
r
)
and stator self-inductance (Ls) is
measured simultaneously without
rotating the motor.
40-70 Sec
When auto-tuning is complete
successfully, “None” is displayed. If error
occurs during auto-tuning, “[][] Error” is
displayed. In this case, verify motor
parameters and encoder setting is done
properly and redo the auto-tuning. If the
problem persists, contact LS
representative.
Total: 3-5
minutes
z FWD/REV LED on keypad will blink during Auto-tuning.
z Motor constants of each can be selected and separately tuned.
(Rs Tuning, Lsigma, Flux Curr, Ls Tuning, Tr Tuning)
PAR AutoTuneType
23 Standstill
PAR Auto tuning
24 ALL1
PAR Auto tuning
24 Rs Tuning
PAR Auto tuning
24 sL Tuning
PAR Auto tuning
24 If/Tr/Ls Tuning
PAR Auto tuning
24 None
PAR Auto tuning
24 [][] Error