6. Function Description
6-5
6.2 DIO Group (DIO_[][])
6.2.1 Jump code (DIO_00)
In I/O_00, jumping directly to any parameter code can be accomplished by entering the desired code number.
(Example) Moving to I/O_05
Press [PROG] and set to 5 using [SHIFT/ESC] / [(Up)] / [(Down)] and press [ENT] key to move to I/O_05. If the
desired code cannot be set, the closest code will be displayed.
Jumping other code is available using [(Up)] / [(Down)] keys.
6.2.2 Multi-function input terminal
1) DIO_01 ~ DIO_07 (Multi-function input terminal P1 ~ P7 define)
It defines Multi-function input terminals. SV-iV5 has 7 dedicated terminals (P1 ~ P7) for the setting of parameters
below. However, the multiple terminals cannot be selected for the same function and if so, the invalid terminal definition
is displayed as “Not Used”. And the selected function cannot be adjusted while running.
No Set value Description No Set value Description
1 Speed-L Multi-step speed-Low 16 Prohibit FWD Forward Run prevention
2 Speed-M Multi-step speed-Middle 17 Prohibit REV Reverse Run prevention
3 Speed-H Multi-step speed-High 18 Proc PID Dis PID operation disabled
4 Jog Speed Jog speed 19 Timer Input Timer ON
5 MOP Up MOP UP operation 20 SoftStrtCncl Cancel Soft start
6 MOP Down MOP Down operation 21 ASR Gain Sel Switch ASR gain
7 MOP Clear MOP Speed Clear (Reset) 22 ASR P/PI Sel Switch ASR P/PI
8 MOP Save MOP Speed Save 23 Flux Ref Sel Switch Flux reference
9 Analog Hold Analog speed ref. Hold 24 PreExcite Pre-excitation
10 Main Drive
Exchange between Option and
Inverter
25 Spd/Trq Sel Speed/Torque control select
11 2nd Func The 2
nd
function 26 Use Max Trq Torque limit ON/OFF
12 Xcel-L Multi-accel/decel-Low 27 Use Trq Bias Torque bias ON/OFF
13 Xcel-H Multi-accel/decel-High 28 Battery Run Selection of battery-operated
14 3-Wire 3 Wire 29 LVT Diable
Detection of Low voltage trip
disabled
15 Ext Trip-B External trip B contact
DIO P5 define
05 Not Used

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LS Industrial Systems SV-iV5 Series and is the answer not in the manual?

LS Industrial Systems SV-iV5 Series Specifications

General IconGeneral
BrandLS Industrial Systems
ModelSV-iV5 Series
CategoryInverter
LanguageEnglish

Related product manuals