6. Function Description
6-6
1.1) Speed-L
1.2) Speed-M
1.3) Speed-H
1.4) JOG operation
By defining P1 ~ P4 as “Speed-L, “Speed-M”, “Speed-H” and “Jog Speed”, the selected references in FUN goup 12 ~
20 (Multi-step speed 0 ~ 7 and Jog speed) become active as speed reference.
(Example) To define Multi-function input terminals P1, P2, P3 as Speed-L, Speed-M, Speed-H and P4 as Jog Speed;
Code LCD display Description
Setting
range
Unit Set value
DIO_01 P1 define Multi-function input terminal P1 define Speed-L
DIO_02 P2 define Multi-function input terminal P1 define Speed-M
DIO_03 P3 define Multi-function input terminal P3 define Speed-H
DIO _04 P4 define Multi-function input terminal P4 define Jog Speed
When multi-step speed 0 (FUN_12: Speed 0) is selected (P1, P2, P3 = OFF), speed reference is input by the method
set in FUN_02 (Analog, keypad 1/2, option). If the jog (FUN_20) is active, inverter operates with jog frequency
regardless of other terminal signal input.
P1 P2 P3 P4 Set Vaule
OFF OFF OFF OFF
FUN_02: keypadÆ FUN_12(Speed 0)
ON OFF OFF OFF FUN_13(Speed 1)
OFF ON OFF OFF FUN_14(Speed 2)
ON ON OFF OFF FUN_15(Speed 3)
OFF OFF ON OFF FUN_16(Speed 4)
ON OFF ON OFF FUN_17(Speed 5)
OFF ON ON OFF FUN_18(Speed 6)
ON ON ON OFF FUN_19(Speed 7)
X X X ON FUN_20(Jog Speed)
1.5) MOP (Motor operated potentiometer) Up
1.6) MOP Down
1.7) MOP Clear
1.8) MOP Save
When multi-function input terminals P1 ~ P7 is set toMOP Up,MOP Down, inverter performs Accel/Decel
Constant Run according to the terminal input. Generally, MOP function is used to adjust the speed simply with terminal
ON/OFF. When MOP UP/Down is selected, inverter ignores FUN_02 setting, and performs MOP operation. To cancel it,
change the defined terminal to “Not Used”. If this function is selected with “Main Drive” function, operating reference is
done by MOP and the rest will be defined by “Main Drive” function. Max speed limit is FUN_04(Max Speed).
If “MOP Save” is entered during MOP operation, the current speed reference value is saved as ”MOP Data” and