4. Trial Operation
4-7
4.5.2 Rotational auto-tuning
1) Precautions
CAUTION
Be sure to remove the load connected to the motor shaft before performing rotational auto-tuning.
Otherwise, it may lead to damage to the motor or bodily injury. DB resistor should be installed because the
inverter repeats abrupt Accel/Decel many times to find the motor constant (Tr) during tuning.
2) Rotational Auto-tuning procedure
LCD Display Description Tuning Time
Set it to “ Rotational ”. -
Auto-tuning starts when it is set to
ALL1 ”.
-
Checks whether the encoder wiring is
properly done and an encoder works
well by rotating the motor at 1500 rpm
in forward direction.
30 ~ 35(Sec)
Stator resistance (Rs) is measured
without rotating the motor.
10 ~ 20(Sec)
The leakage inductance (sL) of the
motor is measured without rotating the
motor.
5 ~ 20(Sec)
The flux current (IF) is measured by
rotating the motor at 1500 rpm.
30 ~ 60(Sec)
Stator self-inductance (Ls) is measured
by rotating the motor at 1500 rpm.
50 ~ 60(Sec)
Accel/Decel is performed repeatedly to
find motor constant (Tr) so that DB
Resistor should be connected before
starting tuning. Otherwise, “Over
Voltage ” trip will occur.
20 ~ 60(Sec)
PAR AutoTuneType
23 Rotational
PAR Auto tuning
24 ALL1
PAR Auto tuning
24 Enc Testing
PAR Auto tuning
24 Rs Tuning
PAR Auto tuning
24 sL Tuning
PAR Auto tuning
24 IF Tuning
PAR Auto tuning
24 Ls Tuning
PAR Auto tuning
24 Tr Tuning