6. Function Description
6-76
Speed set
100%
10V
Voltage input
Speed set
20%
30%
10V
Voltage input
In X1 Change
Initial Value
100%
Out Y1(Bias) Change
Speed set
10V
20%
Voltage input
100%
100%
30%
Speed set
20%
70%
Voltage input
10V
In X2 Change
Out Y2(Gain) Change
Speed set
100%
80%
30%
20%
70%
10V
Voltage input
analog input
For example about multi-function analog input setting , In X1 : 20%, In X2 : 70%, Out Y1 : 30%, Out Y2 : 80%
for the 0 ~ 10V input, analog command changes are as follows.
3) Criterion for command loss of Multi analog input Ai1 (AIO_1)
You can choose criterion for command loss of signal that is fed into multi-function analog input.
Definition
Code Display
Name
Setting
range
Unit Function description
None Do not set analog loss
Half of x1
If the analog input under the 1/2 of set value of
AIO_03 Ai1 In X1 is fed , it means analog loss.
AIO_12 Ai1 Wbroken
Criterion for
command loss of
Multi analog input Ai1
Below x1
If the analog input under set value of AIO_03 Ai1
In X1 is fed , it means analog loss
There are same functions for choosing the criterion of command loss of the other multi-function analog input.