11. Accessories
11-3
11.3 The Selection of Braking Resistor and the Unit
11.3.1 The selection of dynamic braking resistor
Resistor values shown in the following table is calculated on the basis of 150% of rated braking torque, 5% ED 1).
Power rating of resistor should be doubled for resistor frequency 10% ED use. Additional braking unit should be installed
for above SV 300iV5-2 / SV300iV5-4.
Rated Capacity (5% ED)
Inverter
[Ω]
[W]
(2)
SV 022iV5-2 DB 50 400
SV 037iV5-2 DB 33 600
SV 055iV5-2 DB 20 800
SV 075iV5-2 DB 15 1200
SV 110iV5-2 DB 10 2400
SV 150iV5-2 DB 8 2400
SV 185iV5-2 DB 5 3600
SV 220iV5-2 DB 5 3600
SV 022iV5-4 DB 200 400
SV 037iV5-4 DB 130 600
SV 055iV5-4 DB 85 800
SV 075iV5-4 DB 60 1200
SV 110iV5-4 DB 40 2400
SV 150iV5-4 DB 30 2400
SV 185iV5-4 DB 20 3600
SV 220iV5-4 DB 20 3600
9 (1): ED is based on 100 seconds.
9 (2): Rated capacity is based on the self-cooling.
11.3.2 Wiring of the temperature sensor on braking resistor
Temperature sensor is attached in the LSIS braking resistors to prevent the fire.
Terminal of Braking
Resistor
Power Terminal of Inverter Action
B1, B2 P, BR
P7, CM
One of the multi-function input
terminals (P1 ~ P7) should be set to
‘External Fault Signal b Contact’.
Contact is normally ON at the
ambient temperature and is OFF in
case of over-temperature.