7. WEB Control Application
7-28
value of final tension becomes 60[%]. In the boost function, the set value of WEB_23 Boost Input is not always 0,
but it just operates in case of the multi-function input terminal (DIO_01 ~ DIO_07) set to “Boost Enable” being On.
Function
Code
Loader Display Name of Function Set Range Unit
Factory
Default
WEB_22 Boost Type Boost Type
Proportional
Fixed
Proportional
WEB_23 Boost Input Boost Input 0.0 ~ 50.0 % 0.0
6) WEB_24 Stall Type : Stall Type
7) WEB_25 Stall Input : Stall Input
This function is used when Web is wound with the weaker tension than the preset tension. In case of setting
WEB_24 Stall Type to “Fixed”, the set value of tension less WEB_25 Stall Input set value becomes the set value of
final tension. For example, with the taper function unused, if the set value of tension is 50[%], and WEB_24 Stall
Input set value is 20[%], the set value of final tension becomes 30[%]. If WEB_24 Stall Type is set to “Proportional”,
the set value of tension multiplying by WEB_25 Stall Input set value is subtracted. For example, with the taper
function unused, if the set value of tension is 50[%] and WEB_25 Stall Input set value is 20[%], the set value of
final tension becomes 40[%]. In the Stall function, the set value of WEB_25 Stall Input is not always 0, but it just
operates in case of the multi-function input terminal (DIO_01 ~ DIO_07) set to “Stall Enable” in On.
Function
Code
Loader Display Name of Function Set Range Unit Factory Default
WEB_24 Stall Type Stall Type
Proportional
Fixed
Proportional
WEB_25 Stall Input Stall Input 0.0 ~ 50.0 % 0.0