5. Function Code Table
5-4
5.3 Parameter group (PAR_[][])
SETTING DATA
CODE
NO.
Comm.
Addr
CODE NAME
LCD
DISPLAY
RANGE UNIT DEFAULT
Adjustment
During Run
PAGE
PAR_00 - Jump for quick view Jump Code 1 ~ 33 - - Yes
PAR_01 7301 Initialize parameters Para. init
0 (No)
2 (DIS)
4 (PAR)
6 (CON)
8 (AIO)
10 (2ND)
12 (SYN)
1 (All Groups)
3 (DIO)
5 (FUN)
7 (EXT)
9 (USR)
11 (E/L)
13 (WEB)
0 (No) No
PAR_02 - Read parameters Para. read No / Yes No No
PAR_03 - Write parameters Para. write No / Yes No No
6-24
PAR_04 -
Parameter write
protection
Para. lock 0 ~ 255 0 Yes
PAR_05 - Password Password 0 ~ 9999 0 Yes
6-25
PAR_07 7307 Motor capacity selection Motor select
0 (2.2) 1 (3.7)
2 (5.5) 3 (7.5)
4 (11.0) 5 (15.0)
6 (18.5) 7 (22.0)
8 (30.0) 9 (37.0)
10 (45.0) 11 (55.0)
12 (75.0) 13 (90.0)
14 (110.0) 15 (132.0)
16 (160.0) 17 (220.0)
18 (280.0) 19 (315.0)
20 (375.0)
21 (User Define)
1)
kW - No
PAR_08 7308
Motor cap. selection of
USER
UserMotorSel 1.5 ~ 375.0 kW 5.5 No
PAR_09 7309 Motor cooling type Cooling Mtd
0 (Self-cool)
1 (Forced-cool)
- 1 (Forced-cool) Yes
6-26
PAR_10 730A Pulse no. of encoder Enc Pulse 360 ~ 4096 - 1024 No 6-27
PAR_11 730B Encoder direction setting Enc Dir Set
0 (A Phase Lead)
1 (B Phase Lead)
- 0 (A Phase Lead) No 6-26
PAR_12 730C
Encoder error check
enable
Enc Err Chk
0 (No)
1 (Yes)
- 1 (Yes) No
PAR_13 730D
Encoder LPF time
constant
Enc LPF 0 ~ 100 ms 1 Yes
PAR_14 730E
Encoder error detection
time
EncFaultTime 0.00 ~ 10.00 sec 0.00 No
PAR_15 730F
encoder error reference
speed
EncFaultPerc 0.0 ~ 50.0 % 25.0 No
6-27
PAR_17 7311 Motor base speed Base Speed 100.0 ~ 3600.0 rpm 1800.0 No
PAR_18 7312 Motor rated voltage Rated Volt 120 ~ 560 V No
PAR_19 7313 Motor number of poles Pole number 2 ~ 12 4 Yes
PAR_20 7314 Motor efficiency Efficiency 70.0 ~ 100.0 % Yes
PAR_21 7315 Motor rated slip Rated-Slip 10 ~ 250 rpm Yes
PAR_22 7316 Motor rated current Rated-Curr 1.0 ~ 750.0 A Yes
6-29
PAR_23 7317
Auto tuning type
selection
AutoTuneType
0 (Rotational)
1 (Standstill)
0 (Rotational) No
PAR_24 -
Auto tuning range setting
2)
Auto Tuning
None
ALL1/ALL2
Encoder Test
Rs Tuning
Lsigma
Flux Curr
Ls Tuning
Tr Tuning
- None No
PAR_25 7319 Tuning Torque Tune Torque 10.0 ~ 100.0 % 70 Yes
6-30
PAR_26 731A Motor flux current Flux-Curr 70 % to 0.0 ~ PAR_22 A Yes
PAR_27 731B Motor time constant Tr 30 ~ 3000 ms Yes
PAR_28 731C Leakage inductance Ls 0.00 ~ 500.00 mH Yes
PAR_29 731D Leakage coefficient Lsigma 0.00 ~ 100.00 mH Yes
PAR_30 731E Stator resistance Rs 0.000 ~ 5.000 ohm Yes
6-34
PAR_33 7321
Encoder
pulse multiplication
3)
Enc Scale x1 / x16 / x32 / x64 - x 1 No -
1) When PAR_07 (Motor select) is set to “User Define”, PAR_08 (UserMotorSel) will be displayed.
2) If PAR_23 (AutoTuneType) is set to “Standstill”, the order of display in PAR_24 (Auto Tuning) will be NoneÆ ALL1Æ Rs TuningÆ