6. Function Description
6-71
6.7.4 2nd motor parameters related to acceleration and deceleration
Setting range and factory setting value should be referred to FUN_36 to FUN_41.
Code
No.
LCD display Function
Setting
range
Unit Factory setting
2nd_05 2nd Acc S St 2
nd
motor S ratio 1 in accel. start 0.0 ~ 50.0 % 0.0
2nd_06 2
nd
Dec S Ed 2
nd
motor S ratio 2 in accel. end 0.0 ~ 50.0 % 0.0
2nd_07 2nd Dec S St 2
nd
motor S ratio 1 in decel. start 0.0 ~ 50.0 % 0.0
2nd_08 2nd Dec S Ed 2
nd
motor S ratio 2 in decel. end 0.0 ~ 50.0 % 0.0
2nd_09 2nd Acc time 2
nd
motor acceleration time 0.01 ~ 6000.0 sec 10.0
2nd_10 2nd Dec time 2
nd
motor deceleration time 0.01 ~ 6000.0 sec 10.0
6.7.5 2nd motor parameters related to the pulse encoder
Code
No.
LCD display Function
Setting
range
Unit Factory setting
2nd_12 2nd Enc # 2
nd
motor encoder pulse number 360 ~ 4096 % 1024
2nd_13 2nd Enc Dir 2
nd
motor encoder direction set
A Phase Lead
B Phase Lead
A Phase Lead
2nd_14 2nd Enc Chk 2
nd
motor encoder test enable
Yes
No
Yes
2nd_15 2nd Enc LPF
2
nd
motor encoder LPF time
constant
00 ~ 100 ms 1
6.7.6 2nd motor parameters
Code
No.
LCD display Function
Setting
range
Unit
Factory
setting
2nd_17 2nd BaseSpd 2
nd
motor base speed
300.0 ~
3600.0
rpm 1800.0
2nd_18 2nd R-Volt 2
nd
motor rated voltage 120 ~ 560 V
2nd_19 2nd Pole #
the number of poles of the 2
nd
motor
2 ~ 12 4
2nd_20 2nd Mot Eff. 2
nd
Motor Efficiency 70 ~ 100 % 72
2nd_21 2nd R-Slip 2
nd
motor rated slip 10 ~ 250 rpm
2nd_23 2nd Flx Cur 2
nd
motor magnetizing current
0.0~ Inverter
rated current
A
2nd_24 2nd Mot Tr 2
nd
motor rotor time constant 30 ~ 3000 ms
2nd_25 2nd Mot Ls 2
nd
motor stator inductance 0.00 ~ 500.00 mH
2nd_26 2nd Mot sLs 2
nd
motor leakage coefficient 0.00 ~ 10.00 mH
2nd_27 2nd Mot Rs 2
nd
motor stator resistance 0.000 ~ 5.000 ohm
6.7.7 2nd motor miscellaneous parameters
Code
No.
LCD display Function Setting range Unit
Factory
setting
2nd_11 2nd Cool Mtd 2
nd
motor cooling method Same as the 1
st
motor Self-cool
2nd_32 2nd ETH 1min
2
nd
motor 1 min. level for electronic
thermal protection
Same as the 1
st
motor 150
2nd_33 2nd ETH Cont
2
nd
motor continuous level for
electronic thermal protection
Same as the 1
st
motor 100