6. Function Description
6-49
6.4.11 Wait time for restart upon stop
z
Only active when FUN_03 is set to ‘Free-run’ and operating method is ‘Terminal’.
Code LCD display Description Setting range Unit Factory setting
FUN_62 Restart Time Wait time for Restart upon Stop 0.00 ~ 10.00 sec 0.00
FUN_03 Stop mode Stop method
Decel
Free-run
Decel
Even though restart command is input after stopping the operation, inverter does not run until FUN_62 setting time
elapses.
6.4.12 Overspeed error detection
z
Inverter detects error if motor rpm exceeds its limit. User can set the detection level and time of overspeed.
Code LCD display Description Setting range Unit Factory setting
FUN_63 OverSpdLevel Overspeed Detection Level 100.0 ~ 130.0 % 120.0
FUN_64 OverSpd Time Overspeed Detection Time 0.00 ~ 2.00 sec 0.00
z
FUN_63 is based on 100% of FUN_04(Max Speed).
z
When motor speed exceeds FUN_63 (Overspeed Detection Level) and FUN_64(Overspeed Detection Time) elapses,
overspeed error detection is activated.
z
If FUN_64 is set to 0.00(sec) and motor rpm exceeds FUN_63, inverter immediately detects overspeed error.
TIME
FX(or RX)
Motor
Speed
Target speed
Actual speed
ON
OFF OFF
FUN_62(Restart Time)
ON