9) Torque Current reference
The torque reference is converted to the torque current reference. The torque current reference is generated from the
rated current and magnetizing current of the motor.
The initial value of the rated current and magnetizing
current of the motor can be set by
OTIS vector motor parameter that is chosen at PAR_07
Code LCD display Description Setting range Unit Factory setting
PAR_07 Motor Select Motor capacity selection 2.2 ~ 375.0 kW
PAR_22 Rated-Curr Motor rated current 1.0 ~ 750.0 A
PAR_26 Flux-Curr Motor flux current 0.0 ~ 70% of PAR_22 A