4. Trial Operation
4-11
4.7 Operation by Keypad
4.7.1 Parameter setting for keypad operation to rotate the motor at 100 rpm
RUN/STOP command setting by keypad
Operating speed reference setting by keypad
Operating speed setting
4.7.2 Forward / Reverse Run (FWD / REV)
Low speed operation
z Check if motor speed is +100 rpm in the start-up LCD screen after pressing [FWD] key.
z Check if motor speed is –100 rpm in the start-up LCD screen after pressing [REV] key.
z The following table describes the cases of abnormal rotation due to the incorrect wiring of encoder
and/or motor.
Command
Rotating
direction
Speed display Torque display Wiring Status
FX Forward +100.0(rpm) Below +10%
RX Reverse -100.0(rpm) Below -10%
Normal
FX Forward -10 ~ -40(rpm) 150%(Torque Limit)
RX Reverse 10 ~ 40(rpm) -150%(Torque Limit)
Encoder wiring
reversed
FX Reverse -10 ~ -40(rpm) 150%(Torque Limit)
RX Forward 10 ~ 40(rpm) -150%(Torque Limit)
Phase V and W
wiring reversed
FX Reverse +100.0(rpm) Below +10%
RX Forward -100.0(rpm) Below -10%
Encoder and Motor
all reversed
z If A and B phase are reversed, be sure to replace A with B phase wire after checking the pulse
encoder wiring. Or user does not need to change wiring if PAR_11(Enc Dir Set) setting value is
changed from “A Phase Lead” to “B Phase Lead”.
z If Motor wires are reversed, be sure to replace V with W phase wire after checking the motor
output wiring.
z Torque display is on the basis of the no load operation.
FUN Run/Stop Src
01 Keypad
FUN Spd Ref Sel
02 Keypad1
FUN Speed 0
12 100.0 rpm
+100.0rpm SPD
Tq % A
-100.0rpm SPD
Tq % A