5. Function Code Table
5-3
SETTING DATA
CODE
NO.
Com
m.
Addr
CODE NAME
LCD
DISPLAY
RANGE UNIT DEFAULT
Adjustment
During Run
PAGE
DIO_41 7229
Definition of multi-function
Auxiliary output (AX1)
AX1 Define
0 (Not Used)
1 (INV Ready)
2 (Zero Spd Det)
3 (Spd Det.)
4 (Spd Det(ABS))
5 (Spd Arrival)
6 (Timer Out)
7 (LV Warn)
8 (Run)
9 (Regenerating)
10 (Mot OH Warn)
11 (Inv OH Warn)
12 (Spd Agree)
13 (Trq Det.)
14 (Trq Lmt Det.)
15 (OverLoad)
16 (Stop)
17 (Steady)
18 (Brake Output)
23 (WEB Break)
1)
24 (Up To Spd)
1)
25 (False Core)
1)
- 0 (Not Used) Yes
DIO_42 722A
Definition of multi-function
Auxiliary output (AX2)
AX2 Define Same as DIO_41 - 0 (Not Used) Yes
DIO_43 722B
Definition of multi-function
Auxiliary output (OC1)
OC1 Define Same as DIO_41 - 0 (Not Used) Yes
6-17
DIO_46 722E
Fault relay mode selection
(A, B, C)
Relay Mode 000 ~ 111 bit 011 Yes 6-23
DIO_47 722F Zero speed detection level ZSD Level 0.0 ~ 480.0 rpm 10.0 Yes
DIO_48 7230 Zero speed detection band ZSD Band 0.1 ~ 10.0 % 0.5 Yes
6-18
DIO_49 7231 Speed detection level SD Level -3600 ~ 3600 rpm 0 Yes
DIO_50 7232 Speed detection band SD Band 0.1 ~ 10.0 % 0.5 Yes
6-18
DIO_51 7233 Speed arrival band SA Band 0.1 ~ 10.0 % 0.5 Yes
DIO_52 7234 Speed deviation band SEQ Band 0.1 ~ 10.0 % 0.5 Yes
6-19
DIO_53 7235 Torque detection level TD Level 0.0 ~ 250.0 % 0.0 Yes
DIO_54 7236 Torque detection band TD Band 0.1 ~ 10.0 % 0.5 Yes
6-21
DIO_55 7237 Timer On delay time TimerOn Dly 0.1 ~ 3600.0 sec 0.1 Yes
DIO_56 7238 Timer Off delay time TimerOff Dly 0.1 ~ 3600.0 sec 0.1 Yes
6-20
DIO_57 7239 Overload warning level OL Level 30 ~ 250 % 150 Yes
DIO_58 723A Overload warning time OL Time 0 ~ 30 sec 10 Yes
6-21
DIO_59 723B Overload trip selection OLT Select
0 (No)
1 (Yes)
1 (Yes) Yes
DIO_60 723C Overload trip level OLT Level 30 ~ 250 % 180 Yes
DIO_61 723D Overload trip time OLT Time 0 ~ 60 sec 60 Yes
6-23
DIO_62 723E
Inverter overheat warning
temp.
IH Warn
Temp
50 ~ 85 deg 75 Yes
DIO_63 723F
Inverter overheat warning
band
IH Warn Band 0 ~ 10 deg 5 Yes
6-21
DIO_64 7240
Motor overheat warning
temp.
MH Warn
Temp
75 ~ 130 deg 120 Yes
DIO_65 7241
Motor overheat warning
band
MH Warn
Band
0 ~ 10 deg 5 Yes
6-20
DIO_97 7261
How to Run at Lost
command
Lost
Command
0 (None)
1 (FreeRun)
2 (Stop)
- 0 (None) No 6-23
1) Displayed WEB Control mode setting.