6. Function Description
6-7
retained. When the MOP operation resumes, the retained value will be used as speed reference.
“MOP Clear” resets the MOP Data value to “0”. It is used to change the saved value.
(Example) MOP function setting and operation method is as follows;
Code
LCD
display
Description
Setting
range
Unit Set value
DIO_01 P1 define Multi-function input terminal P1 define MOP Up
DIO_02 P2 define Multi-function input terminal P1 define MOP Down
DIO_03 P3 define Multi-function input terminal P3 define MOP Clear
DIO_04 P4 define Multi-function input terminal P4 define MOP Save
(MOP Up/Down example 1) This is used only if terminal ON/OFF is required for speed control.
TIM
E
P1
FX
Motor
Speed
MOP Up
MOP Down
MOP Up
P2
ONOFF
OFF
ON
OFF ON
ONOFF
OFF
OFF
OFF