6. Function Description
6-62
Droop Control Calculation Example
z When Torque Ref is Positive:
Droop Ref speed = ( Torque Ref [%] - Droop Starting Torque[%] ) * Droop Quantity[%]
The result value becomes positive. Therefore, final speed ref value decreases and it should be,
(Speed Ref – Droop Ref speed)
> Droop low limit speed
Droop
Ref speed < (Speed Ref – Droop low limit speed)
Therefore, positive limit is “
Speed Ref- Droop Low Limit Speed”.
z When Torque Ref is Negative:
Droop Ref speed = -( Torque Ref [%] - Droop Starting Torque[%] ) * Droop Quantity [%]
The result value becomes negative. Therefore, final speed ref value increases and it should be,
(Speed Ref – Droop Ref speed)
< Max Motor speed
Droop
Ref speed >-(Max Motor speed - Speed Ref)
Therefore, negative limit is “
Max Motor speed - Speed Ref”.