9. Troubleshooting and Maintenance
9-9
Connect inverter panel grounding connected with motor grounding to the building grounding.
If not, incorrect motor speed may be input due to encoder input noise.
Is too large speed gain assigned to the inverter while motor load is light?
Motor oscillates at stop when PI gain is set much larger than the actual load in CON_03 and CON_04.
Therefore, gain should be set accordingly. Responsiveness increases when P gain is set higher and I lower but
system may become unstable. Gain value varies system but generally set 30 ~ 70% for P gain and set
100 ~ 500ms for I gain.
Increase PAR_13 Enc LPF setting value.
Is there slip present at the connection of encoder and motor shaft?
Poor encoder and motor connection may generate slip. Check the connection is tight.
12) Parameter change is not saved.
Turn the power off and turn it on. If problem persists, contact LS representatives.
13) “Fuse Open” trip occurs constantly.
is the input (line) voltage normal?
Check the line voltage input. If phase to phase unbalance exceeds 2%(greater than 6V for 380V input),
an AC reactor should be provided. Otherwise, inverter may get damaged and A/S fee will be charged during
Warranty period.
is the phase sequence of the output terminal U, V, W correct?
Check the level of the input signal.
Is the motor insulation damaged?
Various types of malfunction occur when the insulation is damaged. In general, operation stops at a certain
speed (and more), overload or “OC-U (V,W)” trip occurs during regenerating. Or motor overheating and
rotating speed oscillates. This condition persists for a while and then “Fuse Open” trip occurs. It marks motor
insulation is damaged. In this case, replace the motor.