Additional UL Marking
ADDITIONAL UL MARKING
1. Short Circuit Rating
“Suitable For Use On A Circuit Capable Of Delivering Not More Than Table1* RMS Symmetrical Amperes,
240 for rated 240V drives or 480 for rated 480V drives
Volts Maximum,” or equivalent.
Table1*
Inverter Capacity Rating
200/400V Class: 5.5kW, 7.5kW, 11kW, 15kW, 18.5 kW, 22kW, 30kW, 37kW 5,000A
400V Class: 45kW, 55kW, 75kW, 90kW, 110kW, 132kW 10,000A
400V Class: 160kW, 220kW 18,000A
2. SHORT CIRCUIT FUSE/BREAKER MARKING
Use Class H or K5 UL Listed Input Fuse and UL Listed Breaker Only. See the table below for the Voltage
and Current rating of the fuses and the breakers.
External Fuse Breaker Internal Fuse
Input
[V]
Inverter
[kW]
Current
[A]
Voltage
[V]
Current
[A]
Voltage
[V]
Current
[A]
Voltage
[Vac/dc]
Manufacturer Model Number
5.5 40 500 50 220 60 250 Hinode Elec 250GH-60
7.5 50 500 60 220 60 250 Hinode Elec 250GH-60
11 70 500 100 220 125 250 Hinode Elec 250GH-125
15 100 500 100 220 150 250 Hinode Elec 250GH-150
18.5 100 500 225 220 175 250 Hinode Elec 250GH-175
22 125 500 225 220 225 250 Hinode Elec 250GH-225
30 150 500 225 220 250 250 Hinode Elec 250GH-250S
200
Class
37 200 500 225 220 250 250 Hinode Elec 250GH-250S
5.5 20 500 30 460 35 660 Hinode Elec 660GH-35
7.5 30 500 30 460 35 660 Hinode Elec 660GH-35
11 35 500 50 460 63 660 Hinode Elec 660GH-63
15 45 500 60 460 80 660 Hinode Elec 660GH-80
18.5 60 500 100 460 100 660 Hinode Elec 660GH-100
22 70 500 100 460 125 660 Hinode Elec 660GH-125
30 100 500 100 460 125 600 Hinode Elec 600FH-125S
37 100 500 225 460 150 600 Hinode Elec 600FH-150S
45 100 500 225 460 200 600 Hinode Elec 600FH-200S
55 150 500 225 460 200 600 Hinode Elec 600FH-200S
75 200 500 225 460 125 600 Hinode Elec 600FH-125S
90 250 500 400 460 200 600 Hinode Elec 600FH-200S
110 300 500 400 460 200 600 Hinode Elec 600FH-200S
132 400 500 400 460 300 600 Hinode Elec 600FH-300S
160 400 500 400 460 300 600 Hinode Elec 600FH-300S
400
Class
220
― ―
600 460 600 600 Hinode Elec 600SPF-600UL
3. FIELD WIRING TERMINAL
1) Use Copper wires only with Copper conductors, 75℃
2) Input and motor output terminal blocks are intended only for use with ring type connectors.
4. CAUTION-Risk of Electric Shock
“Before opening the cover, disconnect all power and wait at least 10 minutes”
Units suitable only for use in a pollution degree 2 environment. Be sure to mount the inverter in a forced-
ventilated operating panel.