6. Function Description
6-2
Code Parameter name LCD display Unit Description
Regeneration Trq Limit Reg Trq Limit % Regeneration torque limit to rated torque
Torque Reference Torque Ref % Torque reference to rated torque
Torque current ref. IqeRef % Torque current reference to rated torque current
Torque current Iqe % Actual torque current to rated torque current
Flux reference Flux Ref % Flux reference to the rated flux
Flux Current ref. IdeRef % Flux current reference to rated flux current
Flux Current Ide % Actual flux current to rated flux current
ACR output of axis Q ACR_Q Out V ACR output value of axis Q
ACR output of axis D ACR_D Out V ACR output value of axis D
Voltage reference of
axis D
VdeRef V Voltage reference value of axis D
Voltage reference of
axis Q
VqeRef V Voltage reference value of Q axis Q
Output current Out Amps RMS A Inverter output current (rms)
Output voltage Out Volt RMS V Inverter output voltage (rms)
Output power Power kW Motor output power
DC LINK voltage DC Bus Volt V Inverter DC link voltage
Process PI reference Proc PI Ref % Reference value of Process PID routine
Process PI Feedback Proc PI F/B % Feedback value of Process PID routine
Process PI output Proc PI Out % Output value of Process PID routine
Motor temperature
NTC
Mot Temp NTC deg
Temp displayed when mot temp sensor is NTC. 25
displayed when temp sensor is not provided with the
motor.
Motor temperature
PTC
Mot Temp PTC deg
Temp displayed when mot temp sensor is PTC. 25
displayed when temp sensor is not provided with the
motor.
Inverter temperature Inv Temp deg Inverter Heatsink temp displayed
Inverter i2t Inv i
2
t %
Inverter overload capability displayed. In the case
Overload capability is 150% for 1 min, i
2
t becomes
100% when 150% of rated current is flowing for 1
min.
MOP output MP Output %
Set value displayed when operation is done by
potentiometer on terminal input.
Control mode Ctrl Mode Selected control mode displayed
Software version S/W Version S/W version displayed
Running time Run Time Inverter running time displayed after Power On
ON/OFF status of Input terminal displayed
(0: OFF, 1: ON)
FX RX BX P1 P2 P3 P4 P5 P6 P7
Input terminal status Terminal In
0 :
OFF
1 :
ON
0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
ON/OFF status of open collector output, fault relay
and contact output.
(0: OFF, 1: ON)
AX1 AX2 OC1 NC NC
30A
(30B)
Output terminal status Terminal Out
0 : OFF
1 : ON
0/1 0/1 0/1 0 0 0/1
DIS_01
~
DIS_03
Running status Run Status Operating status displayed
*1) In the case of using EXTN_I/O, it will be displayed up to Ai5.