6. Function Description
6-31
2.3) Rotational auto-tuning procedure
LCD display Description
Tuning
time
Set it to “ Rotational ”. -
Auto-tuning starts when it is set to “ ALL1 ”. -
Checks whether the encoder wiring is properly
done and an encoder works well by rotating
the motor at base speed in forward direction.
30~35(Sec)
Stator resistance (Rs) is measured without
rotating the motor.
10~20(Sec)
The leakage inductance (sL) of the motor is
measured without rotating the motor.
5 ~ 20(Sec)
The flux current (IF) is measured by rotating
the motor at base speed.
30~60(Sec)
Stator self-inductance (Ls) is measured by
rotating the motor at base speed.
50~60(Sec)
Accel/Decel is performed repeatedly to find
motor constant (Tr) so that DB Resistor should
be connected before starting tuning.
Otherwise, “Over Voltage ” trip will occur.
20~60(Sec)
When auto-tuning is complete successfully,
“None” is displayed. If error occurs during
auto-tuning, “[][] Error” is displayed. In this
case, verify motor parameters and encoder
setting is done properly and redo the auto-
tuning. If the problem persists, contact LS
representative.
Total:
3 ~ 5
(Min.)
PAR Auto tuning
24 [][] Error
PAR Auto tuning
24 ALL1
PAR AutoTuneType
23 Rotational
PAR Auto tuning
24 Tr Tuning
PAR Auto tuning
24 None
PAR Auto tuning
24 Enc Testing
PAR Auto tuning
24 Rs Tuning
PAR Auto tuning
24 sL Tuning
PAR Auto tuning
24 IF Tuning
PAR Auto tuning
24 Ls Tuning