SPECIFICATIONS
3.1 Performance Specifications
3.1.3 Accuracy
3 - 12
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES
BEFORE OPERATION
5
UTILITY PACKAGE
(GX CONFIGURATOR-
AD)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
3.1.3 Accuracy
The reference accuracy is the accuracy at the ambient temperature for offset/gain setting.
The temperature coefficient is the accuracy per temperature variation of 1°C.
The reference accuracy is the accuracy relative to the maximum digital output value.
Even if you change the offset/gain setting or input range to change the input characteristic,
the reference accuracy and temperature coefficient do not change and are kept within the
ranges given in the performance specifications.
[Example] Accuracy when the temperature changed from 25°C to 30°C
0.1% (reference accuracy) + 0.00714%/°C (temperature coefficient) 5°C (temperature
variation difference) = 0.1357%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric GX Configurator-AD (SW2D5C-QADU-E) and is the answer not in the manual?

Mitsubishi Electric GX Configurator-AD (SW2D5C-QADU-E) Specifications

General IconGeneral
BrandMitsubishi Electric
ModelGX Configurator-AD (SW2D5C-QADU-E)
CategoryControl Unit
LanguageEnglish

Related product manuals