3.4 Buffer Memory
3.4.21 CH[ ] rate alarm upper/lower limit value (Un\G126 to Un\G141)
3 - 70
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES
BEFORE OPERATION
5
UTILITY PACKAGE
(GX CONFIGURATOR-
AD)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
3.4.21 CH
[ ]
rate alarm upper/lower limit value (Un\G126 to Un\G141)
(1) For each channel, set the range of change rate of digital output values.
(2) To validate the setting, the operating condition setting request (Y9) must be turned
ON/OFF. (Refer to Section 3.3.2.)
(3) The setting range is -32768 to 32767 (-3276.8 to 3276.7%). Set the value in 0.1%/s
increments.
(4) Refer to Section 3.2.4 for details of the rate alarm.
Example) When setting the rate alarm upper limit value to 30%/s, store 300 into
the buffer memory.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric GX Configurator-AD (SW2D5C-QADU-E) and is the answer not in the manual?

Mitsubishi Electric GX Configurator-AD (SW2D5C-QADU-E) Specifications

General IconGeneral
BrandMitsubishi Electric
ModelGX Configurator-AD (SW2D5C-QADU-E)
CategoryControl Unit
LanguageEnglish

Related product manuals