3.4.14 Warning output flag (Un\G50,Un\51)
(1) If the digital output value or its varying rate falls outside the setting range set to the
CH process alarm upper/lower limit value (Un\G86 to Un\G117) or CH rate alarm
upper/lower limit value (Un\G126 to Un\G141), the warning output flag for the
corresponding channel turns to 1.
(2) For both the process alarm and rate alarm, whether the warning is for the upper or
lower limit value can be checked on a channel basis.
(3) When the digital output value or its varying rate returns to within the setting range, the
warning output flag is automatically reset.
(4) If a warning is detected on any one of the channels for which A/D conversion and
process alarm or rate alarm warning output are enabled, the Warning output signal
(X8) also turns ON.
(5) When the operating condition setting request (Y9) is turned ON, the warning output
flag is cleared.
3.4.15 Scaling enable/disable setting (Un\G53)
(1) Whether to enable or disable the scaling function for each channel is set in this area.
(2) To validate the scaling function, the operating condition setting request (Y9) must be
turned ON/OFF. (Refer to Section 3.3.2.)
(3) All channels are defaulted to "Disable".
When the Scaling enable/disable setting (Un\G53) is set to "Disable", 0s are
stored in the CH scaling value storage area (Un\G54 to Un\G61).
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH2 CH2 CH1 CH1CH4 CH4 CH3 CH3CH6 CH6 CH5 CH5CH8
Un\G50(Process alarm)
CH8 CH7 CH7
0: Normal,
1: Alarm ON
For Q66AD-DG, information of b12 to b15 is fixed at 0.
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
CH2 CH2 CH1 CH1CH4 CH4 CH3 CH3CH6 CH6 CH5 CH5CH8 CH8 CH7 CH7
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
Lower
limit
value
Upper
limit
value
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Un\G51(Rate alarm)
0: Normal,
1: Alarm ON
For Q66AD-DG, information of b12 to b15 is fixed at 0.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Un\G53
For Q68AD-G, information of b8 to b15 is fixed at 0.
For Q66AD-DG, information of b6 to b15 is fixed at 0.
0: Active
1: Inactive
CH4 CH3 CH2 CH1CH8 CH7 CH6 CH500000000

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric GX Configurator-AD (SW2D5C-QADU-E) and is the answer not in the manual?

Mitsubishi Electric GX Configurator-AD (SW2D5C-QADU-E) Specifications

General IconGeneral
BrandMitsubishi Electric
ModelGX Configurator-AD (SW2D5C-QADU-E)
CategoryControl Unit
LanguageEnglish

Related product manuals