6-4-3. Interlocked LOSSNAY settings
The ON/OFF status of the LOSSNAY or OA Processing units can be interlocked with the operation of indoor units.
Note: The ON/OFF status of the indoor units are not interlocked with the ON/OFF status of the LOSSNAY unit.
(1) Click [Unit Settings] > [Interlocked LOSSNAY] to access the interlocked LOSSNAY settings screen.
(2)
Click the icon in “Interlocked LOSSNAY registration” (
) to display the unit address selection screen.
(3) Select the address number of the LOSSNAY to be interlocked, and click [OK].
(4)
Click the icon in “Interlocked indoor unit registration” (
) to display the unit address selection screen.
(5) Select the address number of the air conditioners with whose operations are to be interlocked, and click [OK].
Each LOSSNAY can be interlocked with up to 16 indoor units.
(6) Click [Save] to save the settings.
Interlocked LOSSNAY
registration
Click to display the screen
for registering the LOSSNAY
unit to be interlocked.
Save
Click to save the settings.
Interlocked indoor unit
registration
Click to display the screen
for registering the air
conditioners with whose
operations are to be
interlocked.
Back
Click to display the previous
settings without making any
changes.