5-1-6. Groups
Touch [Initial Settings] in the menu bar, and then touch [Groups].
Register the groups of air conditioning units, LOSSNAY units (ventilators), Air To Water (PWFY) units, AHC, HWHP
(CAHV, CRHV) units, chiller units, or general equipment to be connected to the AE-200/AE-50/EW-50, and then
touch [Save Settings].
Note: Register HWHP (QAHV) units by following the procedure in section 5-1-7 “HW Supply”.
Note: Some settings may not be accessible if logged in as a building manager.
Note: If the system is connected to a TG-2000A, make or change the settings from the TG-2000A.
Note: The [Controller] setting will appear (only on the AE-200’s LCD) when the [System Exp] setting on the [Unit Info.] screen is set
to [Expand]. Switch the [Controller] setting between [AE200] and [Exp1] through [Exp4] to make settings for each AE-200,
AE-50, and EW-50 individually.
Note: When registering LOSSNAY units or OA Processing units, do not combine the units that support Night Purge function and
the units that do not in one group.
Important
● Group settings for the AE-50/EW-50 must be made with the AE-50/EW-50 properly connected to ensure proper settings.
Those settings made without the connection of AE-50/EW-50 will not be reflected.
● The units connected to AE-200 cannot be grouped together with the units connected to AE-50/EW-50.
[1] Setting group names
(1) Touch the “Group name” button to display the keyboard. Enter the group name in 20 alphanumeric or symbol
characters or less.
Note: The following characters cannot be used: <, >, &, “, or ‘
Group No.
Group name
AHC registration
Remote controller
registration
System controller
registration
Save Settings
Touch to save the changes
made.
Controller
Select [AE] to make
settings for AE-200, and
select [1], [2], [3], or [4]
to make settings for each
AE-50/EW-50.
Unit selection