7-3. Functions 2
7-3-1. Set Temperature Range Limit
The settable temperature range for the local remote controllers can be limited. By restricting the lower and upper
limit of the set temperatures for cooling, heating, and auto modes, energy consumption can be reduced.
Click [Functions 2] in the menu bar, and then click [Set Temperature Range Limit] to access the set temperature
range restrictions settings screen.
Note: The set temperature range restrictions settings may not be effective, depending on the unit model of the remote controller
and the indoor unit.
Note: A-control (Mr. Slim) units, room air conditioners, and residential air conditioners do not support the set temperature range
restrictions settings.
Note: The set temperature range restrictions settings may not be accessible if logged in as a building manager.
Note: The set temperature limit range for the AUTO mode cannot be set for the groups that support the dual set point function in
the AUTO mode. The set temperature ranges for the normal cooling and heating modes will be used for the ones for cooling
and heating in the Auto (dual set point) mode.
(1) Scroll up or down to display the group whose settings are
to be made. To make settings for all groups at once, click
[Batch Operations].
Then, click the [Set temperature range] area to display
the setting screen.
Set the temperature ranges for cooling, heating, and auto
modes.
Click [OK] to return to the previous screen.
Note: When the temperature unit is Fahrenheit, temperatures
are displayed in 2ºF increments.
Note: The temperature range for Dry mode will be the same as
the one for cooling mode.
(2) To copy the settings of a group to the settings for other groups, click [Copy] in the row of the group whose
settings are to be copied, then click [Paste] in the row of the group to which the copied settings are to be
pasted. The rectangular icons next to the selected buttons will appear in yellow-green.
(3) Click [Save Settings] to save the settings.
Group No. and
group name
Refresh
Click to import the settings
from AE-200/AE-50/EW-50.
Set temperature range
Batch Operations
Click to make settings for all
groups collectively.
Copy
Paste
Save Settings
Click to save the changes
made.