(3) In the [Indoor unit electricity meter] section, select the electricity meter to be used to measure the electricity
consumption of each group of indoor units.
In the pulldown menu, [“Address”+ PI controller address + “-” + Electricity meter number + Electricity
meter name] will appear when a PI controller (PAC-YG60MCA) is connected, or [“Meter” + Channel No. +
Electricity meter name] will appear when a metering device is directly connected to the controller.
Note: If the electricity meter name is long, only part of it may be displayed.
Note: The electricity meter name will be blank if it has not been registered.
Note: Only the electricity meters whose measurement unit setting is set to [kWh] on the Measurement screen are available
for selection.
Note: When an AE-200 apportioned electricity billing function is used, this setting is not effective because the billing
function settings are used to apportion the electricity consumption.
(4) Click [Save Settings] to save the settings.