EasyManuals Logo

Mitsubishi AE-200A User Manual

Mitsubishi AE-200A
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
51
WT07627X03
5-1-9. Blocks
By making block settings, multiple groups in a given block can be collectively monitored or operated.
Touch [Initial Settings] in the menu bar, and then touch [Blocks]. Register the groups to each block, and then touch
[Save Settings].
Note: Some settings may not be accessible if logged in as a building manager.
Note: If the system is connected to a TG-2000A, make or change the settings from the TG-2000A.
Note: The [Controller] setting will appear (only on the AE-200’s LCD) when the [System Exp] setting on the [Unit Info.] screen is set
to [Expand]. Switch the [Controller] setting between [AE200] and [Exp1] through [Exp4] to make settings for each AE-200,
AE-50, and EW-50 individually.
Note: The ventilation will stop when the Peak Cut control runs for the LOSSNAY units or OA Processing units that perform Night
purge operation. For this reason, do not register the LOSSNAY units and OA Processing units that perform Night purge
operation in the same block.
Important
Block settings for the AE-50/EW-50 must be made with the AE-50/EW-50 properly connected to ensure proper settings.
Those settings made without the connection of AE-50/EW-50 will not be reflected.
(1) Touch the “Block name” button to display the keyboard. Enter the group name in 20 alphanumeric or symbol
characters or less.
Note: The following characters cannot be used: <, >, &, “, or ‘
(2) Touch the “Group registration” button of the target block. A
screen to select the groups will appear.
Touch the group numbers to be registered. (The name of
the group that was touched last will appear.)
The selected group numbers will appear with an orange
frame. Touch again to deselect.
Note: HWHP (CAHV, CRHV, QAHV) unit groups and chiller unit
groups cannot be registered to a block.
Block name
Group registration
Block No.
Group name
Save Settings
Touch to save the changes
made.
Controller
Select [AE] to make
settings for AE-200, and
select [1], [2], [3], or [4]
to make settings for each
AE-50/EW-50.
Group No.
“AE-50 No. - Group No.”
will appear if one or more
AE-50/EW-50 controllers are
connected.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi AE-200A and is the answer not in the manual?

Mitsubishi AE-200A Specifications

General IconGeneral
BrandMitsubishi
ModelAE-200A
CategoryControl Systems
LanguageEnglish

Related product manuals