6-4-5. Energy management block settings
Make the settings for the energy management block (tenant) used as collective unit for the apportioned electricity
billing function.
[1] General descriptions
(1) What is energy management block (tenant)?
An energy management block (tenant) is the unit used for displaying and outputting charge calculation
results.
An energy management block (tenant) is a collection of operation blocks.
An operation block is a collection of groups.
(2) LOSSNAY (including OA Processing unit) settings
Make the settings based on the LOSSNAY system configuration.
Usage Energy management block setting method
LOSSNAY When not interlocked with the operation of
indoor units
To apportion the electric energy, set as energy
management block (tenant). (See [2] (3).)
When interlocked with the operation of
indoor units
No settings are required (cannot be set as a target
for billing function).
Note: The LOSSNAY electric energy will be
apportioned based on the operating status
of the interlocked indoor units.
OA Processing unit When not interlocked with the operation of
indoor units
Set as energy management block (tenant). (See [2]
(3).)
When
interlocked with
the operation of
indoor units
When interlocked with
the operation of same
tenant’s indoor units
Set as same energy management block (tenant)
as the interlocked indoor units. (See [2] (6).)
When interlocked with
the operation of multiple
tenants’ indoor units
Make the settings in one of the following ways:
<Method 1>
Set as independent energy management block
(tenant) and invoice the electricity charges by
including it to common area charges, etc. (See [2]
(6).)
<Method 2>
Exclude these units from the tenant settings.
In this case, the electric energy for OA Processing
units will be apportioned based on the operating
status of the interlocked indoor units.
Energy management block
AE-200 EW-50
Operation block
Group
Group
Operation block
Group

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi AE-200A and is the answer not in the manual?

Mitsubishi AE-200A Specifications

General IconGeneral
BrandMitsubishi
ModelAE-200A
CategoryControl Systems
LanguageEnglish

Related product manuals