(4) Select [ON/OFF/Prohibit/Permit (Pulse signal)] when using a pulse signal to collectively run or stop all the
air conditioning units connected to the AE-200, AE-50, or EW-50, or to collectively prohibit or permit the
operation from the local remote controllers.
9
8
7
6
5
4
3
2
1
Connection to AE-200/AE-50/EW-50 (CN5)
12 or 24 VDC
ON signal
OFF signal
: Pulse generator
Prohibit signal
Permit signal
(Example) ON/OFF
(ON)
Contact ON
Contact OFF
(OFF)
Contact ON
Contact OFF
0.5–1.0 second
(Example) Prohibit/Permit
Stop Run
(Prohibit)
0.5–1.0 second
Contact ON
Contact OFF
Stop
(Permit)
0.5–1.0 second
Contact ON
Contact OFF
Permit
0.5–1.0 second
Prohibit Permit