WT07627X03
(2) For each control level, set the total time in which
the Peak Cut control is performed during every 30
minutes.
Each Peak Cut control is performed for three
minutes. If [6] minutes is selected, three-minute
Peak Cut control will be performed twice during
every 30 minutes.
If any time other than [30] minutes is selected, the
indoor units will operate in rotation so that they will
not perform the Peak Cut control at the same time.
0358 10 15 18 20 23 25 3013 28
(3) To copy the settings of a block to the settings for other blocks, display the block whose settings are to be
copied and click [Copy], then display the block to which the copied settings are to be pasted and click [Paste].
The rectangular icons next to the selected buttons will appear in yellow-green.
When [6] minutes is selected
Group 1
Group 2
Group 3
Control time
min