177
WT07627X03
Note: The air conditioning units in the heating operation will stop and the set temperature will return to the original setting
when the Setback Control period is over or the room temperature rises to the minimum temperature plus 3°C (6°F).
Likewise, the air conditioning units in the cooling operation will stop and the set temperature will return to the original
setting when the Setback Control period is over or the room temperature drops to the maximum temperature minus
3°C (6°F).
(3) To copy the settings of a group to the settings for other groups, click [Copy] in the row of the group whose
settings are to be copied, then click [Paste] in the row of the group to which the copied settings are to be
pasted. The rectangular icons next to the selected buttons will appear in yellow-green.
(4) Click [Save Settings] to save the settings.
Room temp.
21°C (69°F)
Min. temp.
12°C (53°F)
Heat ON
21°C (69°F)
When the temperature drops below the minimum temperature (heating operation)
Heat OFF
Setback
operation
starts.
Heat ON
12°C (53°F)
Max. temp.
Setback Control period
28°C (83°F)
Room temp.
24°C (75°F)
Setback
operation
ends.
Cool ON
24°C (75°F)
Heat OFF
21°C (69°F)
3°C (6°F)
Cool OFF
Setback
operation
starts.
When the temperature rises above the maximum temperature (cooling operation)
Cool ON
28°C (83°F)
Setback
operation
ends.
Setback Control period
3°C (6°F)
Cool OFF
24°C (75°F)