78
WT07627X03
Note: To deselect the selection, select [-- --].
Note: “FAN operation time” is the cumulative duration of time in which the indoor unit is powered on.
Note: “Thermo-ON time” is the cumulative duration of time in which the refrigerant is flowing into the indoor unit.
Note: “Capacity save amount” is the cumulative operation time of the outdoor unit based on its capacity.
Note: Electricity consumption is apportioned based on the electricity consumed by outdoor units. The electricity consumed by
indoor units is not considered.
Note: When an AE-200 apportioned electricity billing function is used, this setting is not effective because the billing function
settings are used to apportion the electricity consumption.
(3) Touch the [Indoor unit electricity meter] button.
Select the electricity meter to be used to measure the
electricity consumption of each group of indoor units.
[“Address”+ PI controller address + “-” + Electricity meter
number + Electricity meter name] will appear when a PI
controller (PAC-YG60MCA) is connected, or [“Meter” +
Channel No. + Electricity meter name] will appear when a
metering device is directly connected to the controller.
Note: To deselect the selection, select [-- --].
Note: If the electricity meter name is long, only part of it may be
displayed.
Note: The electricity meter name will be blank if it has not been
registered.
Note: Only the electricity meters whose measurement unit setting
is set to [kWh] on the Measurement screen are available for
selection.
Note: LOSSNAY unit groups and general equipment (connected
via DIDO controller PAC-YG66DCA) groups are excluded.
(Apportioned calculation is not available for these groups.)
Note: When an AE-200 apportioned electricity billing function is
used, this setting is not effective because the billing function
settings are used to apportion the electricity consumption.
(4) Touch [Save Settings] to save the settings.