9.3 Filter Option
In countries where noise across power lines is a concern, Mold-Masters
recommends that an inline lter is tted. Please contact Mold-Masters for
details.
9.4 Alarm Output
NOTE
This section is not applicable for the MT-02-02 controller.
A HAN4A connector provides an alarm output from an internal set of relay
contacts. Using an external power source the cabinet can initiate a number
of warning devices whenever any zone goes into an alarm state. This
is commonly used for beacons, audible alarms or informing the molding
machine. The contacts are rated for 2A at 125VAC/60VDC.
An input can be accepted through the same connector. It may be used for
Remote Standby mode. For exact details, consult the specication for the
particular model.
Table 9-4 HAN4A Pin Connections
Pin Connection Input / Output
1
Auxiliary Input signal
Standby Port
(Dry Contact
Signal)
2
Auxiliary Input Ground
3
Alarm Output Contact
Normally Open
Dry Contacts
4
Alarm Output Contact
Figure 9-5 HAN4A connector
9-6
© 2020 Mold-Masters (2007) Limited. All Rights Reserved.
WIRING DETAILS
MT Controller User Manual