FP0 HardwareSystem Registers
A-14
Matsushita Electric Works (Europe) AG
Address Name of system register
Default
value
Set value (parameter)
RS232C
port
setting
412 Communication method
setting for RS232C port
K0 Using FPWIN Pro or NPSTGR, select
items from the menu.
Using FP programmer II:
K0: RS232C port is not used.
K1: Computer link mode (when connecting
CNET)
K2: Serial data communication mode (gener-
al port)
413 Communication format setting
for RS232C port
Setting item/Default setting
value
Start code: None
Terminal code: CR
Stop bit: 1 bit
Parity check: With odd
Data length: 8 bits
H3 Using FPWIN Pro or NPSTGR, select items
from the menu.
Using FP programmer II:
Specify the setting contents using H
constants.
15 06
Data length 0: 7 bits 1: 8 bits
Parity check 00: None 01: With odd
11: With even
Start code 0: No STX 1: STX
Terminal code 00: CR 01: CR+LF
10: None 11: ETX
Stop bit 0: 1 bit 1: 2 bits
414 Baud rate
setting for
RS232C port
Setting by
FPWIN Pro
or NPSTGR
ver. 4
H1 0: 19200 bps
1: 9600 bps
2: 4800 bps
3: 2400 bps
4: 1200 bps
5: 600 bps
6: 300 bps
415 Unit number setting for
RS232C port (when
connecting CNET)
K1 K1 to K32 (unit No. 1 to 32)
416 Modem compatibility setting
for RS232C port
H0 Using FPWIN Pro or NPSTGR, select
items from the menu.
Using FP programmer II.
H0: Modem disabled
H8000: Modem enabled
417 Starting address setting for
reception buffer
K0 C10C/C14C/C16C type: K0 to K1660
C32C type: K0 to K6144
RS232C
port
418 Capacity
setting for
C10C/ C14C/
C16C type
K1660 K0 to K1660
setting reception
buffer
C32C/ T32CP
type
K6144 K0 to K6144